Eaton 9130 Specifications
General
Topology Online, double-conversion
Configuration Rackmount
Catalog Number PW9130L1500R-XL2UN
Color Black
Rating (VA/Watts) 1500/1350
Diagnostics Full system self-test
Efficiency >95% in high-efficiency mode; >86% in online mode
UPS Bypass Automatic bypass
Dimensions (H x W x D, inches) 3.4 x 17.3 x 16.9
Weight (lbs) 43
Warranty Two-year factory warranty
Rail Kit Included Included with all rackmount units
Remote Emergency Power off (REPO) Emergency shutdown control through the REPO port
Contents
(Ships with the following items)
1 ready-to-go UPS
Intelligent Power Software Suite CD: (Intelligent Power Manager, Intelligent Power Protector, Network Shutdown Module, LanSafe and Personal Solution-Pac)
USB Cable
Network Card-MS
User Guide
Quick Start Instructions
4-post Rail Kit
Electrical Input
Connection NEMA 5-15P
5-15P
Input Cord 6 ft.
Input Voltage Range 90-138 Vac
Nominal Voltage 120V
Frequency 50/60 Hz
Frequency Range 45–65 Hz
Nominal Current 12.5 A
Breaker Ratings 15A
Generator Compatability Yes
Electrical Output
Output Receptacles (6) NEMA 5-15R
5-15R
On Utility Voltage Regulation ±3% of nominal
On Battery Voltage Regulation ±3% of nominal
Voltage Wave Shape (On Battery) Sine wave
Power Factor 0.9
Frequency Regulation ±3% Hz online
Load Crest Factor 3 to 1
Battery
Optional Extended Battery Module PW9130N1500R-EBM2U
Maximum number of extended battery modules (EBM) 4
Battery Type 48 Vdc; (4) 12V, 9 Ah
Half Load Runtime (in mins) 18
Full Load Runtime (in mins) 7
Battery Replacement Hot-swappable internal and external batteries
Start On Battery Allows start of UPS without utility input
Recharge Time Internal batteries: 3 hours. 1 EBM: 9 hours; 2 EBM: 15 hours; 3 EBM: 21 hours; 4 EBM: 27 hours
Communications
User Interface Graphical LCD with blue backlight and text in English, French, German, Russian and Spanish
LEDs Four status-indicating LEDs
Communication Ports (1) USB, (1) RS-232 serial, Relay output (common alarm standard)
Connectivity Card Network Card-MS
Communications Slot Optional communication slots (BD Slot)
Optional Communication Cards SNMP/Web card for direct control and monitoring in SNMP-based networks, monitoring of UPS status and meters through Web browser interface Relay card for integration to industrial environment and building management systems, remote shutdown for IBM AS/400 systems
Power Management Software Bundled software suite CD
Environmental & Standards
RoHS Compliance Yes
Heat Dissipation (BTU) Line: 750, Bat: 1011
Audible Noise 50 dB
Operating Temperature 0°C to 40°C(32°F to 104°F) in online mode, with linear derating for altitude. NOTE:Thermal protection switches load to bypass in case of overheating
Safety markings UL, cUL, VCCI
EMC Markings FCC Class B, EN55022 Class B
Storage Temperature -20°C (-4°F) to +40°C (104°F) with batteries and -25°C (-13°F) to +55°C (131 °F) without batteries
Relative Humidity 5–90% non-condensing