Eaton 9130 Technical Specifications
Uninterruptible Power Supply
Eaton 9130 tower UPS. 1500 VA / 1350W, 120V, 5-15P input, (6) 5-15R output
Eaton 9130 technical specifications | |
---|---|
General | |
Topology | Online, double-conversion |
Catalog Number | PW9130L1500T-XL |
Color | Black |
Rating (VA/Watts) | 1500/1350 |
Diagnostics | Full system self-test |
Efficiency | >95% in high-efficiency mode; >86% in online mode |
UPS Bypass | Automatic bypass |
Dimensions (H x W x D, inches) | 9.1 x 6.3 x 17 |
Weight (lbs) | 41.8 |
Warranty | Two-year factory warranty |
Contents (Ships with the following items) |
1 ready-to-go UPS Intelligent Power Software Suite CD: (Intelligent Power Manager, Intelligent Power Protector, Network Shutdown Module, LanSafe and Personal Solution-Pac) USB Cable User Guide Quick Start Instructions Cord-Retention Brackets |
Electrical Input | |
Connection | 5-15P |
Input Cord | 6 ft line cord |
Input Voltage Range | 90-138 Vac |
Nominal Voltage | 120 VAC |
Frequency | 50/60 Hz |
Frequency Range | 45–65 Hz |
Nominal Current | 12.5 A |
Breaker Ratings | 15A |
Electrical Output | |
Output Receptacles | (6) 5-15R |
On Utility Voltage Regulation | ±3% of nominal |
On Battery Voltage Regulation | ±3% of nominal |
Voltage Wave Shape (On Battery) | Sine wave |
Power Factor | 0.9 |
Frequency Regulation | ±3% Hz online |
Load Crest Factor | 3 to 1 |
Load Segments | Two configurable, individually controlled receptacles |
Battery | |
Runtime
(minutes) Load (watts)
Show: Mouseover graph for detailed runtime values
Battery runtimes are approximate and may vary with equipment, configuration, battery age, temperature, etc.
|
|
Battery Type | 48 Vdc; (4) 12V, 9 Ah |
Battery Type | VRLA 12V/9 Ah (both internal and external) |
Start On Battery | Allows start of UPS without utility input |
Communications | |
User Interface | Graphical LCD with blue backlight and text in English, French, German, Russian and Spanish |
LEDs | Four status-indicating LEDs |
Communication Ports | (1) USB, (1) RS-232 serial |
Communications Slot | Optional communication slots (BD Slot) |
Optional Communication Cards | SNMP/Web card for direct control and monitoring in SNMP-based networks, monitoring of UPS status and meters through Web browser interface Relay card for integration to industrial environment and building management systems, remote shutdown for IBM AS/400 systems |
Power Management Software | Bundled Intelligent Power Software Suite CD |
Environmental & Standards | |
Heat Dissipation (BTU) | Line: 750, Bat: 1011 |
Audible Noise | 50 dB |
Operating Temperature | 0°C to 40°C(32°F to 104°F) in online mode, with linear derating for altitude. NOTE:Thermal protection switches load to bypass in case of overheating |
Safety markings | UL, CUL, VCCI |
EMC Markings | FCC Class B, EN55022 Class B |
Storage Temperature | -20°C (-4°F) to +40°C (104°F) with batteries and -25°C (-13°F) to +55°C (131 °F) without batteries |
Relative Humidity | 5–90% non-condensing |