Eaton 9355 UPS 20 and 30 kVA Technical Specs
Uninterruptible Power Supply
Battery Runtimes
Model Selection Guide
Options
X-Slot Connectivity Options
Technical Specifications for 20 and 30 kVA1 | |
---|---|
Power | |
Ratings (kVA/Watts) | 20 kVA/18 kW and 30 kVA/27 kW at 0.9 power factor |
Topology | Double conversion |
Electrical Input | |
Nominal input voltage | 208V/120V, 220V/127V +10, -15% 480V/277V, 600V (480+600 with transformer) 400V models also available |
Operating frequency | 50/60 Hz (45 to 65 Hz) |
Input power factor | 0.99 typical |
Input current distortion | 5% THD |
Electrical Output | |
Nominal output voltage | 208/120, 220/120 Vac |
Output voltage regulation | ±1% static; ±4% dynamic with 100% step load recovery within 1 ms response time |
Efficiency | 91%, typical |
Heat dissipation (BTU/hr) | 20 kVA models 6,762 @ 208V and 220V input 10,450 @ 480V and 600V (with input isolation transformer) 30 kVA models: 9,220 @ 208V and 220V input 13,831 @ 480V and 600V (with input isolation transformer) |
Battery | |
Batterytype | 9 Ah, sealed, lead-acid, maintenance-free |
Battery runtime | See battery backup time chart |
Batteryreplacement | Field-replaceable |
Charger | Default is 8A |
General | |
Diagnostics | Full system self-test at startup |
UPS bypass | Automatic on overload or UPS failure |
Parallel for redundancy | Yes, using Powerware Hot Sync technology and capacity |
Dimensionsand weights | See model selection table |
Overload | 150% for 5 sec / 125% for 1 min (online), 110% for 10 min |
Communications | |
LCD display | Graphical LCD with blue backlight |
LEDs | (4) LEDs fornotice and alarm |
Audiblealarms | Yes |
Communication ports | (1) RS-232,(1) relay contact, (1) REPO, (2) environmental input |
Communication slot | (2) X-Slot communication bays |
Power management software | BundledSoftware Suite CD |
Environmental | |
Operating temperature | 50–104ºF (10–40ºC), 45ºC with 7.5% derating; Optimal battery performance: 77ºF (25ºC) |
Storage temperature | 32–77ºF (0–25ºC); Recommended battery storage: 59–77ºF (15–25ºC) |
Relativehumidity | 0–95%, non-condensing |
Audiblenoise | 58 dBA at 1 meter depending on load |
Altitude | 3000m |
Certifications | |
Safety certifications | IEC 62040-1-1, IEC 60950, EN 62040-1-1, UL 1778, NOM-0190SCP8-1993 |
EMCcompliance | EN 50091-2 Class A |
Quality | ISO 9001: 2000 and ISO14001:1996 |
Markings | UL, cUL, NOM-NYCE |
1. Due to continuous product improvements, program specifications are subject to change without notice.
Note: Backup times are approximate and may vary with equipment, configuration, battery age, temperature etc.
1. 50/60 Hz auto-sensing.
2. An input neutral is required for all configurations unless the input isolation transformer is used. For parallel systems, change the fifth CTO digit to a 2 and include parallel tie cabinet.
3. All models include internal batteries.
4. Add 50 lb. to determine shipping weight.
5. Contains on-board maintenance bypass.
6. With isolation transformer.
7. 220V units are wye connected 220/127V input and 220/127V output, three-phase, four-wire plus ground
1. 400A Bus, 200A Neutral, (1) 350A MBP and (4) 110A MIS.
2. Requires Industrial Relay and Display Card. See X-Slot Connectivity Options table
3. Add 40 lb. for shipping weight of panels and 50 lb. for panels with panelboard provisions.
1. The UPS has two X-Slots. One card can be factory installed while the second X-Slot card can be purchased separately.
2. 5A @ 250V. Provides (4) form-C relay contacts for integrating UPS alarms into security and alarm systems. Also provides signal information for the Remote Monitor Display Panel (part number 103002687-001).