Eaton 9355 UPS 10-15 kVA Technical Specs
Uninterruptible Power Supply
Battery Runtimes
Model Selection Guide
Power Distribution Module
Options
X-Slot Connectivity Options
Technical Specifications for 10 and 15 kVA1 | |
---|---|
Power | |
Ratings (kVA/Watts) | 10 kVA/9 kW and 15 kVA/13.5 kW at 0.9 power factor |
Topology | Double conversion |
Electrical Input | |
Nominal input voltage | 208V/120V or 220V/127V three-phase 400V models also available |
Input voltage range | -15%, +10% from nominal at 100% load without depleting battery |
Operating frequency | 50/60 Hz (45 to 65 Hz) |
Input power factor | >0.99 typical, >0.96 frequency converter |
Input current distortion | 5% THD |
Electrical Output | |
Nominal output voltage | 208/120, 220/127 Vac |
Output voltage regulation | ±1% static; ±5% dynamic at 100% resistive load change, < 1 ms response time |
Efficiency | 91%, typical |
Heat dissipation (BTU/hr) | 10 kVA models: 3,798 @ 208V and 220V input 6,294 @ 480V and 600V (with input isolation transformer) 15 kVA models: 5,122 @ 208V and 220V input 8,134 @ 480V and 600V (with input isolation transformer) |
Battery | |
Batterytype | 9 Ah, sealed, lead-acid, maintenance-free |
Battery runtime | See battery backup time chart |
Batteryreplacement | Field-replaceable |
Charger | Default is 3.4A per battery string. Charger current is configurable from 0.5A to 25A per string with an overall maximum of 34A (limited by input current) |
Start-on-battery | Allows start of UPS without utility input |
General | |
Diagnostics | Full system self-test at startup |
UPS bypass | Automatic on overload or UPS failure |
Parallel for redundancy | Yes, using Powerware Hot Sync technology and capacity |
Dimensionsand weights | See model selection table |
Overload (normal operation) | 150% for 5 sec / 125% for 1 min (online), 110% for 10 min |
Communications | |
LCD display | Graphical LCD with blue backlight |
LEDs | (4) LEDs fornotice and alarm |
Audiblealarms | Yes |
Communication ports | (1) RS-232,(1) relay contact, (1) REPO, (2) environmental input |
Communication slots | (2) X-Slot communication bays |
Power management software | BundledSoftware Suite CD |
Environmental | |
Operating temperature | 50–104ºF (10–40ºC), 45ºC with 7.5% derating; Optimal battery performance: 77ºF (25ºC) |
Storage temperature | 32–77ºF (0–25ºC); Recommended battery storage: 59–77ºF (15–25ºC) |
Relativehumidity | 0–95%, non-condensing |
Audiblenoise | 56 dBA at 1 meter (noiseless room) typical |
Altitude | 9,843 ft. (3000m) without derating |
Certifications | |
Safety certifications | IEC 62040-1-1, IEC 60950, EN 62040-1-1, UL 1778 |
EMCcompliance | EN 50091-2 Class A |
Quality | ISO 9001: 2000 and ISO14001:1996 |
Markings | UL, cUL |
1. Due to continuous product improvements, program specifications are subject to change without notice.
Note: Backup times are approximate and may vary with equipment, configuration, battery age, temperature etc.
1. 50/60 Hz auto-sensing.
2. An input neutral is required for all configurations unless the input isolation transformer is used. For parallel systems, change the fifth configure-to-order (CTO) digit to a 2 and include parallel tie cabinet.
3. Add 47 lb. for two-high configurations or 50 lb. for three-high configurations to determine shipping weight.
4. 220V units are wye connected 220/127V input and 220/127V output, three-phase, four-wire plus ground.
1. The combined quantities of LOCKING receptacles (denoted by *) must not exceed four per unit.1. Arrange receptacle codes in numerical-alphabetical order in digits 9 through 12 of the CTO number. Example 1: A PDM with an L21-20, an L14-30, and Qty 2 IEC320-C19 would have digits 9 through 12 of the CTO arranged as "3MPP". Example 2: A PDM with a 5-15R, and an L6-30 and an L14-30 would have digits 9 through 12 of the CTO arranged as “AKMX”. Please be sure utilize the "X" designation for any of the four total slots not populated.
1. 208V/208V input/output voltage. 225A bus, 200A neutral, (1) 225A MBP and (4) 80A MIS.
2. Requires Industrial Relay and Display Card. See X-Slot Connectivity
3. Add 40 lb. for shipping weight of panels and 50 lb. for panels with panelboard provisions.
1. The UPS has two X-Slots. One card can be factory installed while the second X-Slot card can be purchased separately.
2. 5A @ 250V. Provides (4) form-C relay contacts for integrating UPS alarms into security and alarm systems. Also provides signal information for the Remote Monitor Display Panel (part number 103002687-001).