Call a Specialist Today! 833-335-0427

Eaton 5PX Technical Specifications
Uninterruptible Power Supply

Eaton 5PX
Eaton 5PX rack/tower UPS. 3000 VA / 2700W, 2U, 120V, L5-30P input, (1) L5-30R and (6) 5-20R output

Eaton 5PX technical specifications
General
Topology Line-Interactive High Frequency (Pure Sine wave, Buck + Boost)
Configuration Rack/Tower
Catalog Number 5PX3000RT2U
Color Black
Rating (VA/Watts) 3000/2700
Diagnostics Full system self-test at power up
Efficiency

Mouseover graph for detailed efficiency values
UPS Bypass EHBPL3000R-PDU1U (optional)
Dimensions (H x W x D, inches) 3.4 x 17.4 x 25.5
Dimensions (H x W x D, mm) 86 x 441 x 647
Weight (kg) 40
Weight (lbs) 87
Warranty 3 years on electronics, 3 years on batteries with registration
Rail Kit Included Tower stands and 4-post rail kit included
Contents
(Ships with the following items)
5PX3000RT2U
Four-post rail kit
User manual CD
Tower pedestals
Intelligent Power Software Suite CD
Quick start guide
RS-232 serial cable
USB cable
Phillips head screw driver
Electrical Input
Connection (1) L5-30P
L5-30P
Input Cord 10 ft
Input Voltage Range 89–151 Vac (adjustable to 70–153 Vac)
Nominal Voltage 120 Vac (adjustable to100/120/127 Vac)
Frequency 50/60 Hz (auto-sensing)
Frequency Range 47–70 Hz (50 Hz system), 56.5–70 Hz (60 Hz system), 40 Hz in low-sensitivity mode
Input Power Factor 0.9
Electrical Output
Output Receptacles (1) L5-30R
L5-30R
(6) 5-20R
5-20R
On Utility Voltage Regulation 102–132 Vac
On Battery Voltage Regulation -10%, +6% of nominal
Output Frequency 50/60 Hz ±0.1 % (autosensing)
Transfer Time 1–4 ms typical
Load Segments Group 1: (2) 5-20R outlets Group 2: (2) 5-20R outlets
Battery

Runtime
(minutes)
Load (watts)

Show:

Mouseover graph for detailed runtime values


Battery runtimes are approximate and may vary with equipment, configuration, battery age, temperature, etc.
Optional Extended Battery Module 5PXEBM72RT2U
Battery Management ABM® technology and temperature-compensated charging method (user selectable), automatic battery test, deep discharge protection, automatic recognition of extended battery modules (EBMs)
Battery Type 12V/9 Ah; sealed, lead-acid; maintenance free
Battery Replacement Hot-swappable internal batteries and extended battery modules (EBMs)
Start On Battery Allows start of UPS without utility power
Communications
User Interface LCD graphical display
LEDs Load protected, battery and fault
Communication Ports 1 USB HID compliant port + 1 RS232 serial port and relay contacts (USB and RS232 ports cannot be used simultaneously)
Communications Card Slots 1 slot for ConnectUPS-MS network management card
Power Management Software Eaton Intelligent Power Software Suite CD (included)
Environmental & Standards
Heat Dissipation (BTU) Line: 305, Battery: 2047
Audible Noise 50 dBA
Operating Temperature 0°C–40°C (32°F–104°F)
Performance - Safety - EMC UL1778; UL497A; cUL
Safety markings UL, cUL
EMC Markings FCC Part 15 subpart B Class A
Storage Temperature -15°C–50°C (5°F–122°F)
Relative Humidity 20–95% non-condensing
Altitude Up to 10,000 ft (3000m) without de-rating