Eaton 5P 1500 Tower UPS Technical Specifications
Enterprise class battery backup in a space-saving tower design for network closets and computer rooms
The Eaton 5P tower provides premium protection while conserving value space in multiple, slim tower designs.
Eaton 5P 1500 Tower UPS Technical Specifications | |
---|---|
General | |
Topology | Line-interactive |
Configuration | Tower |
Color | Black and silver |
Rating (VA/Watts) | 1440/1100 |
Diagnostics | Full system self-test at power up |
Efficiency | up to 97% |
Dimensions (H x W x D, inches) | 9.1 x 5.9 x 17.5 |
Dimensions (H x W x D, mm) | 230 x 150 x 445 |
Weight (kg) | 16.16 |
Weight (lbs) | 35.6 |
Warranty | 3 years on electronics, 3 years on batteries with registration |
Remote Emergency Power off (REPO) | ROO/RPO: Rear terminal block connector for remote on/off and power off |
Contents (Ships with the following items) |
5P UPS User Manual CD Intelligent Power Software Suite CD Quick start guide USB cable RS-232 serial cable |
Electrical Input | |
Connection | 5-15P |
Input Cord | 6 feet (1.8 meters) |
Input Voltage Range | 89–151 Vac (adjustable to 70–153 Vac) |
Nominal Voltage | 120 Vac (adjustable to 100/120/127 Vac) |
Frequency | 50/60 Hz (auto-sensing) |
Frequency Range | 47–70 Hz (50 Hz system), 56.5–70 Hz (60 Hz system), 40-70 Hz in low-sensitivity mode |
Electrical Output | |
Nominal Voltage | 120V default (100/120/125V) |
Output Receptacles | (8) 5-15R |
On Utility Voltage Regulation | 102–132 Vac |
On Battery Voltage Regulation | -10%, +6% of nominal |
Output Frequency | 50/60 Hz ±0.1 % (autosensing) |
Load Segments | Group 1: (2) 5-15R outlets; Group 2: (2) 5-15R outlets |
Battery | |
Runtime
(minutes) Load (watts)
Mouseover graph for detailed runtime values
Battery runtimes are approximate and may vary with equipment, configuration, battery age, temperature, etc.
|
|
Battery Description | Sealed, maintenance free lead-acid battery |
Battery Management | ABM technology; 3-stage charging extends battery service life by 50% and provides advance warning for battery replacement |
Battery Type | Sealed, lead-acid; maintenance free |
Battery Replacement | Hot-swappable internal batteries |
Extended Battery Capability | None |
Start On Battery | Allows start of UPS without utility power (First time start must be on AC power) |
Communications | |
User Interface | LCD graphical display |
LEDs | Load protected, on battery and fault |
Communication Ports | RS-232 (RJ45) ports; USB port as standard (HID). 6-foot RS-232 and USB cables included |
Communications Card Slots | One slot; Network Card-MS is optional |
Power Management Software | Eaton Intelligent Power Software Suite CD (included) |
Environmental & Standards | |
RoHS Compliance | Yes |
Heat Dissipation (BTU) | Line: 113, Battery 714 |
Audible Noise | 45 dB at 1 meter |
Operating Temperature | 0°C to 40°C (32°F to 104°F) |
Performance - Safety - EMC | UL 1778, UL497A |
Safety markings | cULus, CE |
EMC Markings | IEC 62040-2 C1-C2 / EN 55024 / CISPR22 Class B / FCC part 15 Class B |
Storage Temperature | -15°C – 40°C (5°F – 104°F) |
Relative Humidity | 0–90% non-condensing |
Altitude | Up to 10,000 ft (3000m) without de-rating |